Once the re-close sequence has been performed, the function is automatically reset (it is not
repeated other times till new correct conditions reappear).
In accordance with ANSI, Toc must be less than 300ms independently of Open Command duration
(for convention we can define Toc=200ms). If the open command persists over Toc, another opening
operation will be performed after the OC operation (see dash-line). Twait is less than 1.5 cycles.
Remark: the Re-close is not activated if the Under Voltage function is timing i.e. all the conditions
to operate an Undervoltage open are true.
If the Re-close function is activated but # CB Close Disabling input (default DI 5) is enabled and
active (no voltage on input), the Re-close will not be performed.
In applications that foresee Local/Remote mode selection, the transition from Local to Remote
mode resets the local stored closing positive edge. To perform a re-close it is necessary to activate
the close remote close input. Vice versa, it takes place from Remote to Local mode transition
(remote stored closing positive edge is reset).
CASE1:
normal re-close sequence performed locally by pushbuttons
CASE2:
when the close pushbutton is pressed the ED is ready for a re-closing operation (CB
closed, local). When the Loc/Rem mode input is switched to remote mode the previous
Local Closing positive edge is reset: in this case if an opening command is launched,
the re-close is not performed.
CASE3:
when the close pushbutton is pressed the ED is ready for a re-close operation (CB
closed, local). When the Loc/Rem mode input is switched to remote mode the previous
Local Closing positive edge is reset. To perform the re-close sequence, it is necessary
to have a new Remote Close Command positive edge and the relative Remote Open
command.
Local Close Command
(close pushbutton)
= Independently of the signal level (high or low)
CASE 2
CASE 1
CASE 3
Time
Loc./Rem. mode Input
Local Open Command
(open pushbutton)
Remote Close Command
Remote Open Command
Circuit-Breaker Status
Fig. 35