13
ABB i-bus
®
EIB / KNX
Application and planning
System setup
In “master” mode, the Fan Coil Controller FC/S 1.1 is used to set the heating
and cooling valves as well as to switch the fan outputs. The recording and
regulation of the temperature is carried out at the same time by the Fan Coil
Controller. To do so, the temperature controller TS/K 1.1 is connected to the
Fan Coil Controller (see Fig. 6).
Fig. 6: Fan Coil Controller as “master”
The setpoint adjustment and the toggling of the operation are carried out via
an EIB / KNX operator panel (e.g. MT701.2). To take the drip tray monitoring
and the window contact into account, the sensors can be connected direct-
ly to the Fan Coil Controller.
Configuration as a master
To configure the Fan Coil Controller as a master, the following parameters
must be set:
– Parameter:
Sensor for measuring the actual temperature
(parameter window “Actual temperature”)
Option: “local”
– Parameter:
Setpoint adjustment
(parameter window “Setpoints 1”)
Option: “via EIB”
3.2.2
Fan Coil Controller
as
„master“