Note/Illustration
Action
xx1800001959
Set the Jogging speed to 20% and test the soft-
ware limit.
If the software limit has been set correctly, the
following error should be generated, see the fig-
ure.
6
WARNING
This step should be carried out
with great care. If the software limit
has not been set correctly the
mechanical unit may hit the mech-
anical hard stop.
Repeat the previous steps for the other limit.
7
Offset parameters
The offset parameters for the FlexTrack IRT 501 are manufacturer parameters,
and must not be modified on site.
Continues on next page
Product manual - FlexTrack IRT501-66/66R/90/90R
109
3HAW050008590-001 Revision: C
© Copyright 20042018 ABB. All rights reserved.
2 Installation and commissioning
2.8.6 Set Upper and Lower Limits Software Limits for track
Continued