5.2 Fine calibration
General
This procedure must be applied at the first start or after mechanical intervention
(motor change, gearbox).
Note/Illustration
Action
Using the FlexPendant, jog the carriage close to
the calibration gauge position.
1
xx1800002077
Move the track until the calibration holes line up.
2
xx1800001960
Insert the calibration pin (3HAW107700354).
A dowel pin diameter 8 mm can also be used.
3
Tap
ABB
on the top left of the FlexPendant
4
Tap
Calibration
.
5
Select the desired mechanical unit.
6
Tap
Fine calibration
.
7
Select the desired axis.
8
Tap
Calibrate
.
9
176
Product manual - FlexTrack IRT501-66/66R/90/90R
3HAW050008590-001 Revision: C
© Copyright 20042018 ABB. All rights reserved.
5 Calibration
5.2 Fine calibration