Tip
If the IRC5 reboots without error, then the *.CFG files have been loaded correctly.
If an error occurs, record the error message and error number a send the back
up of the original system, system layout and error information to the
After-Sales
support
to get help.
If the system enters
System failure state
it is necessary to perform a cold start.
This will restore the system to a default settings with no mechanical units or
programs. Then restore the original backup taken before loading the *.CFG files.
Then retry loading the *.CFG files.
98
Product manual - FlexTrack IRT501-66/66R/90/90R
3HAW050008590-001 Revision: C
© Copyright 20042018 ABB. All rights reserved.
2 Installation and commissioning
2.8.2 Load configuration files
Continued