Important
This section contains basic information about flowmeter designs supporting PROFIBUS PA
and FOUNDATION Fieldbus communication. You will find more detailed information in the
supplementary interface descriptions for the meter "PROFIBUS PA interface description" (part
no. D184B093Uxx). These appear on the CD supplied with the meters (part no.
D699D002Uxx), which, if necessary, can be ordered separately from ABB at any time free of
charge.
The fieldbus transmitters are suitable for connection to DP / PA segment couplers and the ABB
MB204 multibarrier. The meter's PROFIBUS PA interface conforms with Profile B V.3.0
(fieldbus standard PROFIBUS, EN 50170, DIN 19245 [PRO91]). The transmitter transmission
signal is designed according to IEC 61158-2. Certification has been obtained to verify
conformity with the standard. The meter's PROFIBUS PA ID no. is 05DC hex. The meter can
also be operated using standard ID numbers 9700 hex and 9740 hex. The meter's intrinsically
safe design conforms to the FISCO model.
Configuration instructions
G00714
x
ε
PLS/SPS
3
3
Profibus DP
1
2
COPA-XE
FV/FS4000
FV/FS4000
COPA-XE
Fig. 42: Typical PROFIBUS PA network
1
I/O level
2
DP / PA bus coupler (with bus
termination)
3
Bus termination
Summary of Contents for FS4000-SR4
Page 125: ...Appendix D184B097U02 FV4000 VT4 VR4 FS4000 ST4 SR4 125 ...
Page 126: ...Appendix 126 FV4000 VT4 VR4 FS4000 ST4 SR4 D184B097U02 ...
Page 127: ...Appendix D184B097U02 FV4000 VT4 VR4 FS4000 ST4 SR4 127 ...
Page 128: ...Appendix 128 FV4000 VT4 VR4 FS4000 ST4 SR4 D184B097U02 ...
Page 129: ...Appendix D184B097U02 FV4000 VT4 VR4 FS4000 ST4 SR4 129 ...
Page 135: ......