Communication
64
FV4000-VT4/VR4 / FS4000-ST4/SR4
D184B097U02
7.3
FOUNDATION Fieldbus communication
The fieldbus transmitters have been designed for connection to special bus power supply units
and the ABB MB204 multibarrier. On the standard design (model ...40), the permissible output
voltage range is 9 ... 32 V DC. On the intrinsically safe design (model ...4A), the voltage is
limited to 9 ... 24 V DC. The device's FOUNDATION Fieldbus interface conforms to standards
FF-890/891 and FF902/90. The transmission signal of the transmitter is designed in accordance
with IEC 61158-2.
The device has been registered by the Fieldbus Foundation and meets all current requirements
(successful completion of the FF Conformance Test, compliance with FF spec. 1.4 and
successful completion of the test with the ITK 4.0). The reg. no. is IT013600. The device is
registered with the Fieldbus Foundation under manufacturer ID 0x000320 and device ID 0x0015
. The device supports LAS functionality. The device's intrinsically safe design conforms to the
FISCO model.
G00717
x
ε
3
3
PLS/SPS
1
2
COPA-XE
FV/FS4000
FV/FS4000
COPA-XE
3
3
H1
Fig. 44: Typical FOUNDATION Fieldbus network
1
I/O level / Linking device
2
Zener barrier
3
Bus termination
Important
In this level, the I/O level also provides the voltage supply for the FOUNDATION Fieldbus
(H1).
Bus termination can also be implemented in the linking device.
Summary of Contents for FS4000-SR4
Page 125: ...Appendix D184B097U02 FV4000 VT4 VR4 FS4000 ST4 SR4 125 ...
Page 126: ...Appendix 126 FV4000 VT4 VR4 FS4000 ST4 SR4 D184B097U02 ...
Page 127: ...Appendix D184B097U02 FV4000 VT4 VR4 FS4000 ST4 SR4 127 ...
Page 128: ...Appendix 128 FV4000 VT4 VR4 FS4000 ST4 SR4 D184B097U02 ...
Page 129: ...Appendix D184B097U02 FV4000 VT4 VR4 FS4000 ST4 SR4 129 ...
Page 135: ......