Parameterization
86
FV4000-VT4/VR4 / FS4000-ST4/SR4
D184B097U02
Buttons
Menu item
Buttons Set parameter Buttons
Configurable
parameters
Comments
„Enter“ „Enter“
„Data“
„Step“
Anzeige
1 groß
1 klein_
Totalizer
Total_
Displays the total value of the totalizer block. The
displayed unit is UNIT_TOTAL.
„Step“
Totalizer
Status_
Displays the actual mode of the totalizer and the
status of the output variables (total status).
„Step“
Adr + State_
Displays the PA address and the status of cyclic
communication (Stop, Clear, Operate).
„Enter““
„Enter“
Zeile 2
Zähler_
Displays the flow totalizer.
„Enter““
„Enter“
Zeile 4
Q
Betriebsart_
Q operating mode:
This operating mode is dependent upon the flow
display in operating volume or standard volume/mass
units.
„Enter“
Kontast
█████
The "Data" and "Step" buttons are used to set the
display contrast.
„Enter“ „Enter“
„Data“
„Step“
Fehler-
register
Netzausfall
14
Totalizer for the number of power failures since first
use.
„Data“
„Step“
. . . . . . . .
. . . . . . . .
Displays any errors that have occurred. Press the
"Enter" button to reset.
„Data“ „Enter“
„Data“
„Step“
Funktions
test
„Step“
Funktion
DIP-Switch
PA-Adr.:50
set by switch
„Enter“
1-7: Bus-Adr.
Protect
„Enter“
8: on = Adr by
swit
„Enter“
8: off = Adr by
bus
„Enter“
x = on - = off
xx------
Displays the current setting of the DIP switches on the
digital panel.
Switches 1-7:
PROFIBUS address
Switch 8:
Defines the addressing mode:
Off = Addressing via bus
On = Addressing via miniature switches 1-7
Note:
A change to the local bus address will only be applied
when the device is switched on.
Summary of Contents for FV4000-VT4
Page 125: ...Appendix D184B097U02 FV4000 VT4 VR4 FS4000 ST4 SR4 125 ...
Page 126: ...Appendix 126 FV4000 VT4 VR4 FS4000 ST4 SR4 D184B097U02 ...
Page 127: ...Appendix D184B097U02 FV4000 VT4 VR4 FS4000 ST4 SR4 127 ...
Page 128: ...Appendix 128 FV4000 VT4 VR4 FS4000 ST4 SR4 D184B097U02 ...
Page 129: ...Appendix D184B097U02 FV4000 VT4 VR4 FS4000 ST4 SR4 129 ...
Page 135: ......