Millennium SC_MAN
Rev 2.0
Minimum Configuration
Some of these settings may duplicate those of the preceding sections if replacing an existing
controller.
Set the following configuration items from the front panel as specified by the customer. SW202
-
8 must
be set to ENABLED for changes to be made from the front panel. This section covers only the basic
operations that must be performed so that the controller is minimally configured.
Table 30 Minimum Configuration
Action to Configure the Minimum Configuration
Step
Configuration Attribute to
Change
Front Panel Menu Path/Action
Customer
Value
DATE/TIME
1
Format
Set the date format: MM/DD/YY, DD/MM/YY, YY/MM/DD,
MM/DD/YYYY, DD/MM/YYYY, YYYY/MM/DD.
2
Month
Set the current month (1
-
12).
3
Day
Set the current day (1
-
31).
4
Year
Set the current year.
NOTE
Please note that the system will validate the entries before the system date is modified.
TIME
5
Format
Set time format: 12 or 24 hour.
6
Time
Set the current time.
7
Daylight
Enables or Disables Daylight Savings.
SYSTEM SHUNT
8
Type
See Shunt Type
Set the shunt type: LOAD, BATTERY, or NONE.
9
mV
Set the shunt mV rating (25, 50, 60, 100, 150 mV).
10
I
Set the shunt rated current (0
-
99999).