Page 110
© Copyright 2023 ABB. All rights reserved.
Millennium SC_MAN
Rev 2.0
33
Reconnect
Set contactor reconnect threshold.
This setting configures the plant voltage at which the
contactor will reconnect to the bus. To prevent the contactor
from re
-
operating when battery voltage increases due to load
removal, a voltage several volts higher than the disconnect
voltage is recommended.
Contactor 2
34
Type
Set contactor Type
-
BATTERY, LOAD or NONE.
35
Disconnect
Set contactor disconnect threshold.
36
Reconnect
Set contactor reconnect threshold.
Contactor 3
37
Type
Set contactor Type
-
BATTERY, LOAD or NONE.
38
Disconnect
Set contactor disconnect threshold.
39
Reconnect
Set contactor reconnect threshold.
Table 30 Minimum Configuration
Action to Configure the Minimum Configuration
Step
Configuration Attribute to
Change
Front Panel Menu Path/Action
Customer
Value
Configure Modem Settings
Configure if BSM6 modem is installed.
Table 31 Modem Settings Configuration
Action to Configure Modem Settings
Step
Configuration Attribute to
Change
Action
Customer
Value
1
Initialization String
11
Set the Initialization String to
AT&FEV.
2
Rings Before Answering
12
Set Rings Before Answering as instructed by the customer.
3
Handshaking
12
Set Handshaking as instructed by the customer.
4
Data Bits
12
Set Data Bits as instructed by the customer.
5
Parity
12
Set Parity as instructed by the customer.
6
Stop Bits
12
Set Stop Bits as instructed by the customer.
7
Time
-
out
12
Set Time
-
out as instructed by the customer.
8
Write Enable
12
Set Write Enable as instructed by the customer.
11
Local/Remote Access (Settings > Communication > Modem)
12
Front Panel (Configure> Communication Ports > Modem) or
Local/Remote Access (Settings > Communication > Modem)