Millennium SC_MAN
Rev 2.0
Table 34 MSC Specifications
-
General
Parameter
Specification
Plant Voltage Measurement
Accuracy
0 to 50 °C (±.05% of full scale + 1 count)
48V Systems: ±40 mV
24V Systems: ±25 mV
48V Systems: ±70 mV
24V Systems: ±40 mV
Resolution
0.01V
Plant Current Measurement (Up to 2
shunts)
Accuracy
Resolution
0 to +50 °C : ±0.5% of full scale
-
40 to +75 °C: ±1.25% of full scale
1A
Temperature Measurement
Thermistor Accuracy
1
-
Wire® Probe Accuracy
Resolution
-
5 to +55 °C: ±2°C
-
40 to +75 °C: ±3°C
-
5 to +55 °C: ±1°C
-
40 to +75 °C: ±3°C
0.1°C
4
-
20mA Input Monitor
Accuracy
Resolution
±100µA
±10.0µA
External Voltage Input (EXT
-
V)
Polarity
Return Reference
Accuracy
Resolution
Scaling (Range)
EXT
-
V
-
Positive voltage with respect to EXT
-
VR input
EXT
-
VR
-
Referenced to Discharge Ground (DG) or Floating
15
with 1% 100ppm/°C external resistors
±1.0% of full scale
0.01VDC
0 to 5Vdc, 0 to 30Vdc, or 0 to 60 Vdc via external resistors
Environmental
Operating Temperature
-
40 to 75 °C (
-
40 to 167 °F)
Storage Temperature
-
40 to 85 °C (
-
40 to 185 °F)
Altitude
-
200 to 13,000 feet (
-
61 to 3962 meters)
Humidity
10% to 95% non
-
condensing
Audible Noise
< 60 dBA
Earthquake Rating
See Safety and Standards below
Controlled Environment
Store and operate this equipment in a controlled environment,
an area where the humidity is maintained at levels that cannot cause condensation
on the equipment, the contaminating dust is controlled, and the steady
-
state
ambient temperature is within the range specified.
Operation Without Batteries
Suitability without Batteries
Suitable for use in power plants with or without batteries.
Loss of AC Power
without Batteries
Loss of ac power causes
•
Controller DC power is lost
•
Controller alarm relays are activated (unpowered)
Recovery from
Loss of AC Power
without Batteries
Restoration of AC power causes
•
Rectifiers return to their configured voltage set point
•
Controller DC power is restored
•
Controller automatically return to its last configuration
Alarm relays reflect actual alarm states
15
Floating means EXT
-
V and EXT
-
VR are isolated from all other circuits.
16
For altitudes above 5000 feet (1524 meters), derate the temperature by 3.6 °F per 1000 feet (0.656 °C per 100 meters).