Page 160
© Copyright 2023 ABB. All rights reserved.
Millennium SC_MAN
Rev 2.0
Table 54 Converter Objects and Attributes
Related Commands
Attribute
MNEM
Type
CHA
OPE
MET
CON
BU
Value
Converter Plant
CON
Identifier
IDE
text
CP1
Description
DES
text
X
X
X
Converter Plant 1
Converter output type
TYP
text
X
X
X
24V or 48V
DC Voltage
VDC
number
X
X
number in volts
DC Current
ADC
number
X
number in amps
Capacity
CAP
number
number in amps
On
-
line Converter Capacity
OLCAP
number
number in amps
Voltage Set
-
Point
VSP
number
X
X
X
48
-
52:50, 23
-
27.2:24 (V)
Internal high voltage shutdown
VSD
number
X
X
X
50
-
60:50, 25
-
30:24 (V)
Current Limit
CLM
number
X
X
X
30%
-
100%
Low Voltage Discon Threshold
DTH
number
X
X
X
20
-
25:23 (V)
Low Voltage Recon Threshold
RTH
number
X
X
X
22
-
27:25 (V)
Low Voltage Disconnect Enable
LVD
number
X
X
X
0:disable 1:enable
Remote standby enable
ROF
number
X
X
X
0:disable 1:enable
Redundancy monitor enable
RME
number
X
X
X
0:disable 1:enable
Converter restart
RSS
number
X
X
1 = do restart
Alarm Sub
-
Objects
Converter Fail Alarm
CFA
attrl
CFA1
Converter Fan Minor
CFN
attrl
CFN1
Converter Fan Major
CFJ
attrl
CFJ1
Distribution Fuse Alarm
DFA
attrl
CDFA1
Id Conflict
DID
attrl
CDID1
Incompatible Converter
ICC
attrl
ICC1
Multiple Convert Fail Alarm
MFA
attrl
CMFA1
High Voltage Alarm
HVA
attrl
CHVA1
High Float Voltage Alarm
HFV
attrl
CHFV1
Low Output Voltage Alarm
VLA
attrl
CVLA1
Converter redundancy loss
RL
attrl
CRL1
Converter
DCC
Identifier
IDE
text
Csr (01
-
188)
26
Description
DES
text
X
X
X
DC Converter sr (01
-
188)
26
Type
TYP
text
as found (10 chars)
DC Current
ADC
number
X
number A
Capacity
CAP
number
number (A)
Status
STT
text
X
X
ON, OFF, STANDBY
27
, VACANT
27
Converter Fail
CFA
number
0:inactive 1:active
Distribution Fuse Alarm
DFA
number
0:inactive 1:active
ID Conflict
DID
number
0:inactive 1:active
25
The user may only set the state to ON, STANDBY, or VACANT
26
s is the shelf or carrier number (0 or 1) or shelf number (0
-
18)
r is the converter number within the shelf or carrier (1
-
6)
27
The user may only set the state to ON, STANDBY, or VACANT