Page 164
© Copyright 2023 ABB. All rights reserved.
Millennium SC_MAN
Rev 2.0
Table 57 Disconnect Contactor Objects and Attributes
Related Commands
Attribute
MNEM
Type
CHA
OPE
MET
CON
BU
Value
Contactor Interface Card
DCN
Identifier
IDE
text
DCNnn (01
-
12)
Description
DES
text
X
X
X
Contactor Interface n
Serial Number
SN
text
Serial number
Board Code
BRC
text
Board code
Status
STT
text
X
NONE, MISSING, OPEN, CLOSED
Contactor Interface Type
TYP
text
X
X
X
NONE, CN1, CN2, CN3, or CN4
30
Contactor
CNT
Identifier
IDE
text
CNn (1
-
4)
Description
DES
text
X
X
X
Defaults:
CN1:LVBD, CN2:LVLD1,
CN3:LVLD2, CN4:LVLD3
Status
STT
text
X
31
NONE, DISCON, CONNECT,
FAILED
Enable
ENA
number
X
X
X
0:disable 1:enable
Disconnect Threshold
DTH
number
X
X
X
20
-
25:22 or 40
-
50:44 (V)
Disconnect delay
DDY
number
X
X
X
0
-
300 minutes
Disconnect automode
DAM
number
X
X
X
0:NONE
1:VOLTAGE
2:TIME
Disconnect remaining time
DTM
number
>0 means going to disconnect
Reconnect Threshold
RTH
number
X
X
X
19.5
-
27:24 or 39
-
55:48 (V)
Reconnect delay
RDY
number
X
X
X
0
-
300 minutes
Reconnect automode
RAM
number
X
X
X
0:NONE
1:VOLTAGE
2:TIME
Reconnect remaining time
RTM
number
X
X
X
X
>0 means going to disconnect
Alarm Sub
-
Objects
Contactor Open Alarm
CNO
attrl
CNOn (1
-
4)
Contactor Failed Alarm
CNF
attrl
CNFn (1
-
4)
30
Default contactor interface type: DCN01 = CN1, DCN02 = CN2, DCN03 = CN3, DCN04
-
DCN08 = CN4
31
A contactor configured as a LOAD type cannot be disconnected via a software command. A contactor configured as a BATTERY type may be disconnected via a
software command only if another contactor is also configured as a BATTERY type.