Table 61 Events Objects and Attributes
Related Commands
Attribute
MNEM
Type
CHA
OPE
MET
CON
BU
Value
User Defined Event
UDE
Identifier
IDE
text
Unnnn (0001
-
1500)
Description
DES
text
X
X
X
30 char
Alarm State
AST
number
X
0:inactive 1:active
Severity
SEV
text
X
X
X
CRIT, MAJ, MIN, WRN, RO
Program Line
PRG
text
X
X
X
“” (60
characters)
Minimum Duration
DUR
number
X
X
X
number (seconds)
Latched
LAT
number
X
X
X
0:no 1:yes
LED
LED
text
X
X
X
“”,
BATT, BD, DIST, RECT, AC, RM, or
CTLR
Contact Closure
ACC
text
X
X
X
“”,
ACF, MJF, MNF, RFA, VLV, HV, BD,
CTLR, UR1, or UR2
Notify Delay
DLY
number
X
X
X
0
-
540 (seconds)
Notify On Occur
NOO
number
X
X
X
0:no 1:yes
Notify On Retire
NOR
number
X
X
X
0:no 1:yes
NAG On Occur
NAG
number
X
X
X
0:no 1:yes
Notify Destination
DST
text
X
X
X
“”,
P1, P2, P3, P4
Time Event
TME
Identifier
IDE
text
Tnn (01
-
32)
Description
DES
text
X
X
X
Timer Event n
Status
STT
number
0:inactive 1:active
Date
DAT
date
X
X
X
date
Time
TIM
time
X
X
X
time (default: 11:59am)
Duration
DUR
number
X
X
X
1
-
1440 (minutes)
Maintenance Reminder
MRM
Identifier
IDE
text
MRnn (nn=1
-
12)
Description
DES
text
X
X
X
Maintenance Reminder n
Alarm State
AST
text
0=not active 1=active
Severity
SEV
text
WRN
Notify On Occur
NOO
number
X
X
X
0:no 1:yes
Notify On Retire
NOR
number
X
X
X
0:no 1:yes
NAG On Occur
NAG
number
X
X
X
0:no 1:yes
Notify Destination
DST
text
X
X
X
“”,
P1, P2, P3, P4
Notification Date
DAT
date
X
X
X
01/01/1992
Notification time
TIM
time
X
X
X
12:00AM
Text
TXT
text
X
X
X
“”
Connected Equipment Alarm
CEA
Identifier
IDE
text
CEAn (1
-
6)
Description
DES
text
X
X
X
Connected Equip Alarm n
Alarm State
AST
number
X
0:inactive 1:active
Severity
SEV
text
X
X
X
CRIT, MAJ, MIN, WRN, RO
Notify Delay
DLY
number
X
X
X
0
-
540 seconds
Notify On Occur
NOO
number
X
X
X
0:no 1:yes
Notify On Retire
NOR
number
X
X
X
0:no 1:yes
NAG On Occur
NAG
number
X
X
X
0:no 1:yes
Notify Destination
DST
text
X
X
X
“”,
P1, P2, P3, P4