Page 179
© Copyright 2023 ABB. All rights reserved.
Millennium SC_MAN
Rev 2.0
Table 72 System Objects and Attributes
Related Commands
Attribute
MNEM
Type
CHA
OPE
MET
CON
BU
Value
User
USR
Identifier
IDE
text
USRn (01
-
14), ADM1
Description
DES
text
X
X
X
User Account n (1
-
14)
Administrator Account
Password
PWD
text
X
X
“”
ADM1
-
“
ADMINISTRATOR
”
User name
USR
text
X
X
“”
ADM1
-
“
admin
”
Security level
LVL
text
X
X
“”,
USER, SUPER
-
USER,
ADMINISTRATOR
ADM1
-
ADMINISTRATOR
Call Back Security
CBS
Identifier
IDE
text
CB1
Description
DES
text
X
X
X
Call
-
Back Security 1
Status
STT
number
X
X
X
0:off 1:on
Call
-
Back Phone Number
PHn (1
-
5)
text
X
X
X
digit ( ) * #
-
, space (default:
“”)
Connect Baudrate
BRn (1
-
5)
number
X
X
X
300, 1200, 2400, 4800, 9600, 19200
Notepad
NPD
Identifier
IDE
text
UNP, SNP, ENP
Description
DES
text
X
X
X
User Notepad
Super
-
User Notepad
Easy View Notepad
Notify State
STT
number
X
X
X
0:don
’
t notify 1:notify
Comment Line
CLnn (01
-
15)
text
X
X
X
“”
Alarm Cut Off
ACO
Identifier
IDE
text
ACO1
Description
DES
text
X
X
X
Alarm Cut
-
off
Status
STT
number
X
X
0:disable 1:enable
Critical ACO State
CST
number
0:inactive 1:active
Critical ACO Enable
CAE
number
X
X
X
0:disable 1:enable
Critical ACO Timeout
CTO
number
X
X
X
1
-
4 (hours)
Major ACO State
JST
number
0:inactive 1:active
Major ACO Enable
JAE
number
X
X
X
0:disable 1:enable
Major ACO Timeout
JTO
number
X
X
X
1
-
4 (hours)
Minor ACO State
NST
number
0:inactive 1:active
Minor ACO Enable
NAE
number
X
X
X
0:disable 1:enable
Minor ACO Timeout
NTO
number
X
X
X
1
-
72:8 (hours)
Local Buzzer Enable
LBE
number
X
X
X
0:disable 1:enable
Alarm Sub
-
Objects
ACO Active
AAC
attrl
AAC1
User Defined Object
UDO
Identifier
IDE
text
Onnn (1
-
100)
Description
DES
text
X
X
X
User Object n
User Defined Object Build example
Users
“
build
”
their user defined objects by following the example below:
Command
Comment
ADD UDO,CELL1
-
Add a user defined object called CELL1 to the system
ADD CELL1,TEMP
-
Add the attribute TEMP to CELL1
LIN CELL1 TEMP,C701
-
Link a temperature monitor channel to CELL1 TEMP