Page 57
© Copyright 2023 ABB. All rights reserved.
Millennium SC_MAN
Rev 2.0
Step
Action to Remove Alarm and Control Wiring
TB2 and TB3 are located on the rear of the Galaxy SC controller (see Figure 26)
Figure 30 Galaxy SC TB2 and TB3
NOTE
STOP!
Before proceeding with this step, verify that ABS supply (pins 30, 31, 46, and 47) is not
connected to anything.
If there are connections to ABS perform proper transitioning procedures and move these
connections to another source.
1
Mark, Tag, Remove, and Insulate all connections terminating on TB2 and TB3. You may need
to reference a controller product manual for labeling the connections.