Page 64
© Copyright 2023 ABB. All rights reserved.
Millennium SC_MAN
Rev 2.0
Record MCS DIP Switch Settings
Step
Action to Record MCS DIP Switch Settings
Figure 35 MCS Auxiliary Board (CP2)
1
Remove the ED83006 (auxiliary circuit card) from the MCS.
Is the ED83006 equipped with DIP switches S1, S2, and S3?
2
Yes –
Proceed.
No –
Nothing to record.
Proceed to Remove the MCS Controller.
3
Record the setting values of DIP switches S1, S2, and S3 in Table 16.
•
Float/BD/L2 setting from S1
•
HV/float shutdown settings from S2
•
HV/equalize settings from S3
Table 16 MCS DIP Switch Settings
DIP Switch
Default
Use Table
Threshold
Value
S1 BD
51.25 /25.50
Table 17
Battery on Discharge
S2 HV
53.00 / 26.00
Table 18
High Voltage
-
Float
S3 HV
55.00 / 28.50
Table 19
High Voltage
-
Equalize