Page 85
© Copyright 2023 ABB. All rights reserved.
Millennium SC_MAN
Rev 2.0
Thermal Probes
Without thermal probes, many of the controller
’
s battery management features will not function, or
produce erroneous results. Some features requiring thermal inputs are:
•
Slope Thermal Compensation
•
Reserve Time Prediction
•
High Temperature Alarm
•
Ambient High and Low Temperature Alarms
•
High Temperature Disconnect
NOTE
•
There are several controller thermal probe inputs.
•
There are several types of thermal probes.
•
The type of probe used determines where it is connected on the controller.
•
Any temperature channel may be configured as Battery Temperature.
See the Battery Temperature Measurement section in Features Reference.
Table 27 Thermal Probe Types
Type of Probe
Controller Connection Location
10/30K Thermal Probe
aka UBT (Universal Battery Temperature Probe
P3
1
-
Wire® Voltage / Temperature Devices
P7
10K Thermal Probe additional Terminal Block Interface
(also known as Controller Temperature Channels)
TB2 Pin
Description
1
Probe 2
2
Probe 2 RTN
3
Probe 3
4
Probe 3 RTN
5
Probe 4
6
Probe 4 RTN
10K Thermal Probe
BIC cards in GPS bays
(J12 GP to Rectifiers)
100K RPM Temperature Probes
RPM modules
(TB1 RPM serial bus)
Table 28 P3 Compatible Temperature Probe Cables
Cable Assembly
Used with
848152997
KS20472 round cell thermistor
848152989
ring or paddle type thermistor