Page 92
© Copyright 2023 ABB. All rights reserved.
Millennium SC_MAN
Rev 2.0
Remote Peripheral Monitoring (RPM)
Remote Peripheral Monitoring (RPM) provides data acquisition capability far beyond that normally
available in a power system controller. Monitoring modules available consist of:
•
Shunt monitors (6 ch 1 temperature channel)
•
0
-
100mV dc Voltage monitors (6 ch 1 temperature channel)
•
0
-
3V dc Voltage monitors (6 ch 1 temperature channel)
•
0
-
16V dc Voltage monitors (6 ch 1 temperature channel)
•
0
-
200V dc Voltage monitors (6 ch 1 temperature channel)
•
Temperature monitor (7 Channels)
•
Control Relay module (3 sets of programmable form C relay outputs)
The user may connect a maximum of 95 of any combination of these modules serially.
Step
Action to Connect Remote Peripheral Monitoring (RPM)
NOTE
The Remote Peripheral Monitoring (RPM) feature has been designed into the MCR1B card and
requires no additional circuit cards. Monitoring and control modules ARE required, based on
the application.
NOTE
This section only describes a single module connection to the controller. Modules MUST BE
PROGRAMMED after they have been installed or they may not function properly.
1
Wrap the RPM bus cable (ordering code 407377704) through the EMI inductor bead twice
Place the bead approximately 3 inches from the end of the cable.
2
Terminate the RPM bus cable end with the EMI bead to TB1 on the controller:
*connections of the bus wire are NOT polarity sensitive.
TB
-
1 Pin
TB
-
1 Pin
Descriptions
RPM Conductor
Color
RPM Conductor Description
6
*RPM
Blue or White
Power/Communications
8
*RPM
Blue or White
Power/Communications
9 or 10
FGND
Bare wire
Shield
3
Run the RPM bus cable to the first RPM mounting location.
4
Mount the RPM module connection unit (base).
5
Route the wires through the open
-
faced bottom of the RPM connection unit (base).
6
Terminate the wires on TB2 on the RPM connection unit (base):
•
Connections of the bus wire are NOT polarity sensitive.
•
There are 2 IN, and 2 OUT connections. Either one may be used.
RPM TB
-
2 Pin
RPM Conductor Color
RPM Conductor Description
IN
Blue or White
Power/Communications
OUT
Blue or White
Power/Communications
SHIELD
Bare wire
Shield