Page 21
© Copyright 2021 ABB. All rights reserved.
Torque Settings for Hardware
Table 3
-
A: Torque Settings for Hardware
Unpacking
-
Location
Before continuing, verify that the following conditions exist at the installation site:
·
Floor is conditioned and clean (refers to removal of any combustible flooring, e.g., carpet, wood, etc.)
·
Batteries and associated stands are in place.
·
Cable rack not supported by cabinets is in place.
·
Job Site Documentation is available that details cabinet locations, dc distribution assignments, and
Remote Peripheral Monitoring System module location and assignment.
Metric
Screw Size
Torque (N·m)
Torque (in·lbs)
M2
0.24
2
M2.5
0.48
4
M3
0.9
8
M3.5
1.4
12
M4
2
18
M5
4
35
M6
7
62
M8
18
145
M10
34
300
M12
58
513
English
Screw Size
Torque (N·m)
Torque (in·lbs)
6
-
32
1.1
10
8
-
32
2.3
20
10
-
32
2.8
25
12
-
24
4
35
1/4
-
20
7
65
5/16
-
18
15
135
3/8
-
16
27
240