Page 54
© Copyright 2021 ABB. All rights reserved.
Millennium II Controller Configuration of BIC Shunt Channels
(continued)
4.
Select the “Click to Update” button of the appropriate BIC Shunt channel. A separate pop
-
up menu
specific for the selected input will appear for editing.
5.
Edit/verify all appropriate configuration settings which include:
·
Shunt Current and Voltage values.
·
Shunt Type
·
Shunt Type will typically be set to “Battery” if the assigned shunt is measuring Battery
string charge (
-
) or discharge (+) current in a distributed architecture plant.
·
Shunt Type will be set to “Load” (shown above) only when using the ED83311
-
30 overhead
bus arrangements with Distribution
-
only cabinets each fed by their own shunt. When this is
the case, Shunt Type for Plant Current & Plant Shunt 2 Current on the Settings
-
> Shunts
web page (below) must both be set to None and the “Total System Load Monitored by Re-
mote Shunts” checkbox there must be selected.
·
Click the “Submit Channel” button to ensure all changes are saved.
·
Repeat for all BIC monitored software configured Shunt channels.
Set both to
NONE