Description 

Provides  remote  circuit  breaker  trip  indication 

using  a  single  pole  double

 

throw

 

switch 

actuated  by  the breaker  mechanism.

NOTE: 

Bell  alarm  cannot  be  installed  in  left 

pole of circuit  breaker  models  earlier  than Jan 

1,  1979  (date  code 

D

901*).  Refer  to  factory 

if in  doubt. 

Installation 

CAUTION: 

The  breaker  must  be  completely 

de

 

energized  and  disconnected  from  the 

electrical  circuit, when  the  be

ll

  alarm  is  being 

installed.

 

This  is  mandatory  because  the 

breaker must  be  in  the ON  position  while  the 

accessory is being installed. 

Place  the  breaker  in  a  TRIPPED  position

 

(handle at midpoint) by rotating trip button.

Remove  cover  mounting  screws  (4)  and

 

handle (Figure 2).

Figure  1 

Figure  2 

1

GEH457

6

 INSTALLATION INSTRUCTIONS

 

B

ell

 

A

larm

 

S

witch

 

A

ccessory

For Types  TED, THED

4  COVER SCREWS

(8  FO

R  THLC1 AND 

TLB1)

1.