Note position of accessory mounting holes.
(Figure 3).
Install accessory as shown (Figure 4).
Adjust switch lever so that it actuates switch
within dimension shown with circuit breaker
in reset position. Trip the breaker by pushing
trip bar forward. Switch should actuate. if
not, readjust.(Figure 4).
Make two notches in cover, one for lever
clearance, and one for lead exit as shown in
Figure 5. Affix identification label.
Replace handle and breaker cover, taking care
not to pinch wires or switch lever between
cover and case.
Check continuity of bell alarm switch as
shown in Figure 6. Repeat Step 5 if necessary.
CIRCUIT
BREAKER
IN RESET OR
OFF POSITION
—
Figure 3
—
Figure 4
2
.01" TO .03" TRAVEL MUST
ACTUATE SWITCH
3.
4.
5.
6.
7.