background image

Note  position  of  accessory  mounting  holes. 

(Figure 3).

Install accessory as shown (Figure 4).

Adjust switch lever so that it actuates switch 

within  dimension  shown  with  circuit  breaker 

in reset position. Trip the breaker by pushing 

trip  bar  forward.  Switch  should  actuate.  if 

not, readjust.(Figure 4).

Make  two  notches  in  cover,  one  for  lever 

clearance,  and  one  for  lead  exit  as  shown  in 

Figure 5. Affix identification label.

Replace handle and breaker cover, taking care

not  to  pinch  wires  or  switch  lever  between 

cover and case.

Check  continuity  of  bell  alarm  switch  as 

shown in Figure 6. Repeat Step 5 if necessary.

CIRCUIT 

BREAKER 

IN RESET OR 

OFF POSITION 

Figure 3 

Figure 4 

2

.01" TO .03" TRAVEL MUST 

ACTUATE SWITCH 

3.

4.

5.

6.

7.

8.

Reviews: