background image

2

Reinstall  the  breaker  top  cover,  ensuring  that  the  Trip 
Unit and aluminum accessory sleeve are properly aligned 
with the cover. Tighten the four #10-32 screws to 32 in-
lbs.
Replace the trim plate and tighten the four #8-32 screws 
to 20 in-lbs.
If it is a draw-out breaker, rack it back in.

Trouble-Shooting

The  following  guide  is  provided  for  and  isolating  common 
problems. It does not cover every possible situation. Contact 
the Customer Support Center at 800-843-3742 if any problem 
is not resolved by these procedures.  

Partially Obscure  Counter Display 

The Mechanical 

Counter does not 

advance  with  operation of the 
breaker. 

The first digit of the Mechanical 
Counter is  partially obscured  in 
the  top  cover window,  as in 
Figure  4. 

Symptom

Figure  3.  Mechanical  counter  installed in  breaker. 

1SQC930025M0201, GEH6280 

 

December

 2019

Figure 4.  Counter partially obscured in top cover  window. 

 

ABB Inc. 

 

305 Gregson Drive

 

Cary, NC 27511. 

electrification.us.abb.com

  

 

We reserve the right to make technical 
changes or modify the contents of this 
document without prior notice. With 
regard to purchase orders, the agreed 
particulars shall prevail. ABB Inc. does not 
accept any responsibility whatsoever for 
potential errors or possible lack of 
information in this document. 

We reserve all rights in this document and 
in the subject matter and illustrations 
contained therein. Any reproduction or 
utilization of its contents – in whole or in 
parts – is forbidden without prior written 
consent of ABB Inc.  
Copyright© 2019 ABB  
All rights reserved 

 

GE is a trademark of GE. Manufactured 
by ABB Inc. under license from GE. 

Apply control power to the accessories, then follow the 
normal procedure to recharge the springs and turn the 
breaker on. 

12.

Possible Cause

The  spring-loaded  Mechanical 
Counter  arm  is not  above  the  tab 
on the ON-OFF flag. 

The  Mechanical  Counter  is  out  of 

adjustment on  the mounting plate. 

Corrective Action

See  step  6  of the  installation 

instructions. 

Measure  the interference.  Remove  the 

breaker  top cover  and  the  Mechanical 
Counter  assembly.  Loosen the  two 
screws holding  the  Counter to  the 
mounting plate. Slide  the  Counter over  by 
the amount of the interference.  Tighten 
the two  Counter mounting screws  to  10 
in-lbs, then  reinstall the  Counter  as  per 
the installation instructions. 

9

.

10

.

11

.

Reviews: