Voltage 

Number 

Rating

 

(1) 

Peak Inrush 

Current, mA(2)

Nominal RMS 

Current, mA 

SPST480 

480 Vac 

375 

21 

SPST600 

600 Vac 

300 

17 

SPSTL480  480 Vac 

750 

20 

SPSTL600  600 Vac 

600 

16 

(1)

Rated for 50/60 Hz. Rating is 120 Vac without
step-down transformer.
Peak inrush current is present for 2-6 ms after activation. This 
number is provided so that fuses and supplies can be chosen 
appropriately. 

(2)


Table 1. Catalog numbers and voltages for the  Shunt Trip and Shunt Trip with Lockout

Voltage 

Peak Inrush

Accessory 

Rating 

Current, A 

Nominal RMS 

Current, mA 

Shunt Trip 

120 Vac 

1.5 

85 

Shunt Trip/ 

120 Vac 

80 

Lockout 

Figure 1. Shunt Trip with  Lockout

1

AVERTISSEMENT: 

Les  modules  de  d

é

clenchement  shunt 

480  Vac  et  600  Vac  doivent 

ê

tre  utilis

é

s  avec  le 

transformateur abaisseur de tension qui est fourni.

AVERTISSEMENT:

 Avant d'installer 

 

tout accessoire, mettre 

le  disjoncteur  en  position  OFF,  le  d

é

connecter  de 

toute  tension 

d'alimentation, 

et 

d

é

charger 

l

es 

ressorts d'armement. 

WARNING:

  Before  installing  any  accessories,  turn  the 

breaker  OFF,  disconnect  it  from  all  voltage  sources,  and 
discharge the charging springs. 

The  Shunt  Trip  or  Shunt  Trip  with  Lockout  will  cause  the 
circuit  breaker  to  trip  when  the  control  voltage  is  greater 
than  55%  of  the  rated ac  value. Control power  to  the  Shunt 
Trip  must  be  removed  before  the  breaker  can  be  closed. 
Control  power  to  the  Shunt  Trip  with  Lockout  must  be 
removed  for  a  minimum  of  0.25  second  before  the  breaker 
can be closed. 

Catalog


Table 2 Voltage and current ratings for the 120 Vac Shunt Trip and Shunt Trip with 
Lockout. 

Installation

The  Shunt  Trip  and  Shunt  Trip  with  Lockout  accessories, 
shown in Figure1, can be installed in 800-4000 ampere frame 
Power Break® II circuit breakers. These accessories allow the 
breaker to be tripped electrically from a  remote location. 
In addition to providing a trip signal to the  breaker, the  Shunt 
Trip accessories can be set up    to interact with other Power 
Break II accessories, when used with a MicroVersaTrip Plus or 
MicroVersaTripPM Trip Unit. DIP switches on  the  rear of   the 
breaker Trip Unit can configure the Shunt Trip accessories to 
activate a    Bell Alarm-Alarm Only accessory or    a  Bell   Alarm 
with  Lock  out  accessory  when  a  shunt  trip  occurs.  The 
Accessory Configuration section below describes how this can 
be done. If the breaker is equipped with a  Power+Trip Unit, it 
is configured so that only protection trips will  activate a Bell 
Alarm 

­ 

Alarm Only or  Bell Alarm with Lockout.

The catalog numbers for the Shunt Trip and Shunt Trip with 
Lockout for 480 and 600Vac are listed  in Table 1. Voltage and 
current  ratings  in  Table1  are  given    at    the  input  of    the 
transformer. The voltage and current ratings of  the input to 
the  accessory are equal to that of  the 120Vac version of  the 
accessory.  Table 2 Iists these ratings.

GEH

6519 

INSTRUCTIONS

Power Break® II Circuit Breaker Accessories

 

Shunt Trip and Shunt Trip with Lockout 480& 600Vac 

Introduction

Operation

Apply control voltage to  the  primary of  the  supplied step-
down transformer. The secondary of   the transformer is 
connected to  terminals 31 and 32 of the terminal strip on  the 
right side of  the breaker.

WARNING:  480  Vac  and  600  Vac  Shunt  Trip  accessories 

must be used with the supplied step-down transformer 

Summary of Contents for GE SPST480

Page 1: ...Trip and Shunt Trip with Lockout Installation The Shunt Trip and Shunt Trip with Lockout accessories shown in Figure1 can be installed in 800 4000 ampere frame Power Break II circuit breakers These accessories allow the breaker to be tripped electrically from a remote location In addition to providinga trip signal to the breaker the Shunt Trip accessories can be set up to interact with other Power...

Page 2: ...urs The configuration can be changed by removing the Trip Unit from the breaker setting the DIP switcheson the rear of the Trip Unit and reinstallingthe Trip Unit Figure 4 illustrates the Trip Unit rear DIP switches and their functions Table 4 lists the switch functions and the factory settings for each Use the followingprocedure to installthe Shunt Trip accessory into the Shunt Trip slot of the a...

Page 3: ...dure 1 Turn off the power to the Shunt Trip 2 Close the breaker contacts 3 Apply at least 55 of the rated ac voltage to the Shunt Trip the breaker should trip immediately 4 If a Bell Alarm Alarm Only or Bell Alarm with Lockout is present ensure that they activate or do not activate as selected by the MicroVersaTrip Plus or MicroVersa Trip PM Trip Unit DIP switches Figure 4 Accessory switch on the ...

Page 4: ...ip Unit would be powered up by an energized Shunt Trip accessory Verify that the breaker is closed Check that the Shunt Trip with Lockout control power is applied at greater than 55 of the rated ac voltage Check that the accessory is completelyinserted re insert if necessary Note that an otherwise underpowered Trip Unit is powered by an energized Shunt Trip accessory Check that the Shunt Trip with...