Page 49
© Copyright 2023 ABB. All rights reserved.
GPS2436_MAN
Rev. 1.3
Voltage Threshold Ranges and Default Values
Low
High
Default
Very Low Voltage (VLV)
24V
20.00
25.50
23.00
48V
40.00
51.00
46.00
Battery on Discharge (BD)
24V Float
23.00
28.00
25.00
24V Boost
23.00
28.00
25.00
48V Float
46.00
55.00
51.00
48V Boost
46.00
55.00
51.00
High Float Voltage (HFV)
24V Float
24.75
29.75
26.50
24V Boost
25.75
31.75
26.50
48V Float
50.00
60.00
53.00
48V Boost
52.00
60.00
53.00
High Voltage Shutdown Alarm (HV)
24V Float
24.75
29.75
26.8
24V Boost
25.75
31.75
26.8
48V Float
50.00
60.00
53.6
48V Boost
52.00
60.00
53.6
Rectifier On Threshold (ROT)
24V
20.00
25.00
22.00
48V
40.00
51.00
44.00
Table 9
-
I: Voltage Threshold Ranges and Default Values
Controller Alarm Severity, LED and Relay Default Values
Symbol
Default Designation
Default Severity
Default LED
Default Relay
AAC
ACO Active
RO
None
None
ABS
Alarm Battery Supply Fuse
Major
CTLR
CTLR
AMJ
Auxiliary Major
Major
None
None
AMN
Auxiliary Minor
Minor
None
None
ATA
Alarm Test Active
RO
None
None
ATB
Alarm Test Aborted
RO
None
None
ATF
Alarm Test Failed
Warning
None
None
BBL
Memory Backup Battery Low
Warning
None
None
BCA
Battery Type Conflict
Warning
None
None
BDA
Battery on Discharge
Major
BD
BD
BFA
Battery Test Failed
Minor
BAT
None
BID
Bay Interface ID Conflict
Major
CTLR
CTLR
BTA
Battery Test Active
RO
BD
BD
BTJ
Battery Thermal Major
Major
BAT
None
Table 9
-
J:Controller Alarm Severity, LED and Relay Default Values (Continued)