5.
Rectifiers
Setpoint
This value sets the system voltage for all serial
rectifiers. Move the cursor to the field and use the <+>
or <
-
> key to adjust the threshold value. Press
<ENTER> to save the change.
HVSD
The configuration of this field sets the internal high
voltage shutdown value of all serial rectifiers. Move
the cursor to the field and use the <+> or <
-
> key to
adjust the threshold value. Press <ENTER> to save the
change.
6.
Batteries
Model
The configuration of this field selects the installed
battery type from a list of pre
-
defined battery types
used in reserve time prediction and enhanced battery
test features. Move the cursor to the field and use
the <+> or <
-
> key to adjust the threshold value. Press
<ENTER> to save the change.
Strings
The configuration of this field selects the number of
battery strings in the system. This parameter is used
in reserve time prediction and enhanced battery test
features. Move the cursor to the field and use the <+>
or <
-
> key to adjust the threshold value. Press
<ENTER> to save the change.
Cells/String
The configuration of this field selects the number of
installed cells in the battery strings. This parameter is
used in reserve time prediction and enhanced
battery test features. Move the cursor to the field
and use the <+> or <
-
> key to adjust the threshold
value. Press <ENTER> to save the change.