Rectifier
Rectifier Specifications
1.
With Galaxy Millennium Controller
2.
Factory default settings –
actual range is 44
-
58Vdc
Electrical
Input
Voltage Range
95
-
275Vac, 2
-
wire, single phase
Frequency Range
45
-
66 Hz
Power Factor
> 0.98 at > 50% rated output
AC Surge Protection:
It is important that ac surges reaching rectifiers do not exceed the capacity of the rectifier internal surge
protection. Protection must be provided external to the GPS system, if necessary, to limit surge energy reaching the rectifiers.
Site surge protection must be coordinated with rectifier internal surge protection and must clamp at a lower voltage than the
rectifier internal protection. The internal protection voltage and current characteristics of the rectifiers are as follows:
Output
Internal Selective High Voltage Shutdown (ISHVSD)
High Voltage Shutdown (HVSD)
Float: 56.0Vdc Nom.
1,
2
Boost: 58.5Vdc Nom.
1,
2
Float: 57.00Vdc
Output
Output Power
2726W maximum
Output Current
1
50Adc maximum from
-
40°C to +55°C 30Adc at +75°C
Rectifier derates at approximately
1 ampere per degree C (+55°C to +75°C)
Float/Boost Voltage
44
-
58Vdc
Total Harmonic Distortion
<5% at full load
Regulation
±0.5%
Ripple
100 mVrms
Current Limit Set Point
15A
-
55A
Phase to Phase Voltage
MOV Conduction Current
320Vac(RMS)
0A
620V maximum clamping
1mA (DC test current)
810Vpeak
100A peak
Summary of Contents for GPS4827
Page 12: ...Page 12 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 20: ...Page 20 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 24: ...Page 24 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 30: ...Page 30 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 34: ...Page 34 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 62: ...Page 62 Copyright 2021 ABB All rights reserved Control and Operations Menu Map ...
Page 63: ...Page 63 Copyright 2021 ABB All rights reserved Status Menu Map ...
Page 64: ...Page 64 Copyright 2021 ABB All rights reserved History Menu Map Statistics Menu Map ...
Page 80: ...Page 80 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 82: ...Page 82 Copyright 2021 ABB All rights reserved This page intentionally left blank ...
Page 90: ...Page 90 Copyright 2021 ABB All rights reserved This page intentionally left blank ...