Installation and maintenance guide
1ZSC000563-AAB EN, REV. 6, 2019-09-12
49
Dissipation factor, tan δ
The dissipation factor varies with the temperature of the bushing core, and thus the measured dissipation
factor must be multiplied with the correction factor given below.
Bushing core temperature °C
Correction factor to 20 °C (IEC)
0-2
0.76
3-7
0.81
8-12
0.87
13-17
0.93
18-22
1.00
23-27
1.07
28-32
1.14
33-37
1.21
38-42
1.27
43-47
1.33
48-52
1.37
53-57
1.41
58-62
1.73
63-67
1.43
68-72
1.42
73-77
1.39
78-82
1.35
83-87
1.29
Procedure
1.
De-energize the transformer.
2.
Disconnect the external connections from the outer terminal of the bushing.
3.
Remove the cover (2).