50
Installation and maintenance guide
1ZSC000563-AAB EN, REV. 6, 2019-09-12
4.
Connect the measuring equipment.
1.
Connect the low voltage cable to the stud (1).
2.
Connect the high voltage cable to the
outer terminal.
3.
Connect the ground cable to the bushing
flange (3).
G0051
18
5.
Measure the capacitance (C
1
) between the outer terminal and the stud (1).
•
Record the capacitance (C
1
) for future reference.
NOTE!
Refer to the table for the nominal capacitance (C
1
),
Nominal capacitance,
page
6.
Measure the capacitance (C
2
) between the stud (1) and the flange.
•
Record the capacitance (C
2
) for future reference.
7.
Measure the dissipation factor:
1.
Start the measurements with a low sensitivity setting on the measuring bridge.
2.
Gradually increased the sensitivity setting on the measuring bridge to the highest possible.
3.
Calculate the dissipation factor with the correction factor, refer to
Dissipation factor, tan δ,
page
NOTE!
In some cases, external interference can make it difficult to set the measuring bridge
to zero.
8.
Install the cover (2).
CAUTION!
The voltage tap is not self-grounding!
The bushing can be destroyed if the voltage tap is not grounded. Because the capacitance
(C
2
) is usually relatively small, the voltage tap must never be open-circuited when applying
a voltage to the bushing. It must always be grounded or connected to an external
impedance.
CAUTION!
Do not energize the bushing without the cover or a test adapter installed. The cover
connects the outermost conductive foil to ground and will prevent damage to the bushing.
CAUTION!
Make sure that the cover is correctly installed with the O-ring in place, when the bushing is
not in use. The purpose is to prevent dust and water from entering the tap.
Summary of Contents for GSBK 170
Page 46: ...46 Installation and maintenance guide 1ZSC000563 AAB EN REV 6 2019 09 12 ...
Page 52: ...52 Installation and maintenance guide 1ZSC000563 AAB EN REV 6 2019 09 12 ...
Page 54: ...54 Installation and maintenance guide 1ZSC000563 AAB EN REV 6 2019 09 12 ...
Page 62: ...62 Installation and maintenance guide 1ZSC000563 AAB EN REV 6 2019 09 12 ...
Page 66: ...66 Installation and maintenance guide 1ZSC000563 AAB EN REV 6 2019 09 12 ...
Page 70: ......
Page 71: ......