41-971.3M
Type HCB-1 Pilot Wire Relay System
18
APPROXIMATE RESISTANCE VALUES OF COMPONENTS IN HCB-1 RELAY
Transformer
Secondary Winding
Start to Tap 20 to 30 ohms
Start to Finish 110 to 140 Ohms
Polar Unit
Operating Coil
290-320
Polar Unit
Restraining Coil
Maximum 12 - 16 ohms
Minimum 9 - 12 ohms
Resistor
R
C
41 - 44 ohms
Tube Resistor
R
0
Total of 1.6 ohms
Formed Resistor
R
1
0.131 ohms
Rectifiers
IN91 Germanium Diodes
Indicating Contactor
Switch
0.2 amp. Tap 6.5 ohms
2.0 amp. Tap o.15 ohms
Summary of Contents for HCB-1