5.7.5 General specifications of fixed circuit-breakers
with rh lateral operating mechanisms for ABB UniSec switchgear (12 - 17.5 - 24 kV)
Circuit-breaker
HD4/R-SEC 12
HD4/R-SEC 17
HD4/R-SEC 24
Standards
IEC 62271-100
•
•
•
CEI EN 62271-100
(dossier 7642)
•
•
•
Rated voltage
Ur [kV]
12
17.5
24
Rated insulation voltage
Us [kV]
12
17.5
24
Withstand voltage at 50 Hz
Ud (1 min) [kV]
28
38
50
Impulse withstand voltage
Up [kV]
75
95
125
Rated frequency
fr [Hz]
50-60
50-60
50-60
Rated thermal current (40°C)
Ir [A]
630
800
630
800
630
Rated duty breaking capacity
(symmetrical rated short-circuit current)
Isc [kA]
12.5
12.5
12.5
–
12.5
16
16
16
16
16
20
20
20
(5)
20
(5)
20
25
25
–
–
–
Short-time withstand current (3 s)
Ik [kA]
12.5
12.5
12.5
–
12.5
16
16
16
16
16
20
(3)
20
20
(5)
20
(5)
20
25
(4)
25
(4)
–
–
–
Making capacity
Ip [kA]
31.5
31.5
31.5
–
31.5
40
40
40
40
40
50
50
50
50
50
63
63
–
–
–
Sequence of operations
[O - 0.3s - CO - 15s - CO]
•
•
•
Opening time
[ms]
45
45
45
Arcing time
[ms]
10...15
10...15
10...15
Total break-time
[ms]
55…60
55…60
55…60
Closing time
[ms]
80
80
80
Overall dimensions
(maximum)
H [mm]
740
740
740
L [mm]
315
315
315
D [mm]
1049
1049
1049
Pole center-distance [mm]
230
230
230
Weight
(1)
[kg]
103
103
103
Absolute gas pressure (nominal duty value)
[kPa]
380
380
380
Application of PR521 protection device
In [A]
application not available
Application of REF 601 protection device
•
(2)
•
(2)
•
(2)
Standardized dimensions table
1VCD003536
1VCD003536
1VCD003536
Wiring diagram
with / without REF 601
1VCD400119
1VCD400119
1VCD400119
Operating temperature
[°C]
- 5 ... + 40
- 5 ... + 40
- 5 ... + 40
Tropicalization
IEC: 60068-2-30, 60721-2-1
•
•
•
Electromagnetic compatibility
IEC 62271-1
•
•
•
(1)
increase the indicated weight by 20 kg for circuit-breakers with REF 601 devices and 3 current sensors (15 kg only with 2 current sensors)
(2)
the REF601 device and the current sensors are available on request. The rated current of the REF 601 must be set in the relay and must be compatible with the rated current of the
circuit-breaker. The rated current that can be set with CEI 0-16 is 80 A or 250 A. With the CEI 0-16 version of REF 601, the circuit-breaker is always supplied with 3 phase sensors
(Rogowsky coils) on the circuit-breaker itself, one 40/1 A closed-core toroidal TA and a -MU undervoltage release for relay-controlled opening
(3)
at 12 and 17.5 kV and at 630 A rated current, the rated short-time withstand current is 20 kA for 1 second
(4)
at 12, the rated short-time withstand current is 25 kA for 2 seconds
(5)
at 17.5 kV, the breaking capacity is 21 kA and the rated short-time withstand current is 21 kA for 3 seconds
H
L
D
Summary of Contents for HD4/R
Page 2: ......
Page 21: ...21 7 9 Overall dimensions 7 9 1 Fixed HD4 R 12 24 kV 630 1250 A TN 7237 Figure 9 ...
Page 22: ...22 7 9 2 Fixed HD4 R 12 24 kV 630 1250 A TN 7234 Figure 10 ...
Page 24: ...24 7 9 4 Plug in HD4 S 12 24 kV 630 1250 A TN 7236 Figure 12 ...
Page 25: ...25 7 9 5 HD4 Uniair 12 24 kV 630 1250 A TN 7235 Figure 13 ...
Page 26: ...26 7 9 6 HD4 Uniair F 12 24 kV 630 A TN 7275 Figure 14 ...
Page 27: ...27 7 9 7 HD4 Uniair 2R 12 24 kV 630 1250 A TN 7274 Figure 15 ...
Page 28: ...28 7 9 8 HD4 Uniair A 12 24 kV 630 1250 A TN 7273 Figure 16 ...
Page 29: ...29 7 9 9 HD4 UniMix F 12 24 kV 630 1250 A TN 7366 Figure 17 ...
Page 30: ...30 7 9 10 HD4 R SEC 12 24 kV 630 800 A 1VCD003536 Figure 18 ...
Page 37: ......