background image

31

Carry out the following operations before putting the circuit-
breaker into service: 
–   make sure that the power connections to the circuit-break-

er terminals are tight; 

–   establish the setting of the primary electronic overcurrent 

release (if provided); 

–   make sure that the value of the power supply voltage of the 

auxiliary circuits is between 85% and 110% of the rated 
voltage of the electrical applications; 

–   make sure that there are no foreign bodies, such as bits of 

packing, in the moving parts; 

–   to  avoid  overtemperatures,  make  sure  that  there  is  a  suf-

ficient exchange of air in the place of installation; 

–   also perform the inspections indicated in the following ta-

ble:

8. Putting into service 

  All the operations for putting into service 

must be carried out by ABB personnel or by 
the customer’s qualified personnel.

 

If the operations are obstructed in any way, 
do not force the mechanical interlocks and 
check that the operating sequence is correct. 

 

The operating forces which can be applied 
are indicated in paragraph 6.3.

 

Discharge the closing springs (close and 
open the circuit-breaker) to access the inside 
of the operating mechanism.

 

Disconnect the PR521 release (if provided) 
before conducting insulation tests on the 
circuit-breaker.

8.1  General procedures 

Subject of the inspection 

Procedure

Positive check

1

Insulation resistance.

Medium voltage circuit

Using a 2500 V Megger, measure the insulation 
resistance between the phases and between 
phases and earth the circuit.

The insulation resistance should be at least 50 M

 

and must remain constant over time.

Auxiliary circuits

Using a 500 V Megger (installed equipment 
permitting), measure the insulation resistance 
between the auxiliary circuits and the earth.

The insulation resistance should be several M

 and 

must remain constant over time.

2

Auxiliary circuits.

Make sure that the connections to the control 
circuit are correct: proceed with the relative power 
supply.

Normal operations and signals.

3

Manual operating mechanism.

Perform a few closing and opening operations (see 
chap. 6).

NOTE.

 Power the undervoltage release and the 

locking magnet on the operating mechanism at the 
relative rated voltage (if provided).

The operations and relative signals occur correctly.

4

Motor operator (if provided)

Power the spring loading gearmotor at the relative 
rated voltage.

The springs are loaded correctly.
The signals are correct.
The gearmotor stops when the springs have been 
loaded.

Perform a few closing and opening operations.

NOTE.

 Power the undervoltage release and the 

locking magnet on the operating mechanism at the 
relative rated voltage (if provided).

The gearmotor reloads the springs after each 
closing operation.

5

Undervoltage release (if provided).

Power the undervoltage release at the relative rated 
voltage and perform the circuit-breaker closing 
operation.

The circuit-breaker closes correctly.
The signals are correct.

Disconnect the power supply to the release.

The circuit-breaker opens.
The signal changes over.

6

Opening release.

Close the circuit-breaker.
Power the shunt opening release at the relative 
rated voltage.

The circuit-breaker opens correctly.
The signals are correct.

7

Shunt closing release (if provided).

Open the circuit-breaker. Power the shunt closing 
release at the relative rated voltage.

The circuit-breaker closes correctly.
The signals are correct.

8

Key lock.

Open the circuit-breaker. 
Turn the key and remove it.
Attempt the circuit-breaker closing operation.

Neither manual nor electric closing takes place.

Insert the key again and turn it through 90°.
Perform the closing operation.

Both electric and manual closing take place 
correctly; in this position the key cannot be 
removed.

9

Auxiliary contacts in the operating 
mechanism

Insert the auxiliary contacts into suitable signalling 
circuits.
Perform a few closing and opening operations.

The signals occur correctly.

Summary of Contents for HD4/R

Page 1: ...perating and signalling parts 17 6 3 Instructions for circuit breaker operation 17 7 Installation 19 7 1 General information 19 7 2 Normal installation conditions 19 7 3 Preliminary operations 19 7 4 Installation of fixed circuit breakers 19 7 5 Installation of plug in circuit breakers 19 7 6 Power circuit connections 19 7 7 Earthing 20 7 8 Connection of the auxiliary circuits 20 7 9 Overall dimen...

Page 2: ......

Page 3: ...that the installations are constructed in accordance with the rules of good workmanship and safety in the work place Responsible behaviour safeguards your own and others safety Please contact the ABB Assistance Service for any further requirements Strictly comply with the instructions in this manual Make sure that the rated performance of the apparatus is not exceeded during service Make sure that...

Page 4: ...Mix HD4 R SEC circuit breakers are also designed for different installation configurations However these devices can be subjected to further technical construction modifications at the customer s request so as to adapt them to special installation requirements Consequently the manual may not contain instructions con cerning special customized configurations Besides this manual it is therefore alwa...

Page 5: ...n position with the springs discharged and with the absolute pressure of the pole corresponding to the service value Each piece of apparatus is protected by a plastic cover to prevent water from infiltrating during the loading and unloading stages and to keep the dust off during storage ...

Page 6: ... supply includes all the materials described in the shipping note and the lever for loading the springs of the operating mechanism in the manual mode Should any damage or irregularity be noted in the supply on unpacking notify ABB directly or through the agent or supplier as soon as possible and in any case within five days of receipt The apparatus is only supplied with the accessories specified a...

Page 7: ...ely it must be re packed in the original packing materials Insert at least one standard packet of special hygroscopic substance per piece of apparatus inside the packing Should the original packing no longer be available and the apparatus cannot be installed immediately it should be stored indoors in a well ventilated dry dust free noncorrosive environment well away from any easily flammable mater...

Page 8: ...t breaker on a pallet or a sturdy supporting surface Before proceeding with any operation always make sure that the springs of the operating mechanism spring are discharged and that the apparatus is in the open position When handling the apparatus take great care to prevent the insulating parts and the terminals of the circuit breaker from being stressed Figure 2 ...

Page 9: ...The metal frame is equipped with wheels for 36 kV circuit breakers and for circuit breakers for UniSwitch UniAir UniMix and UniSec switchgear Each pole consists of an epoxy resin enclosure which houses all the active parts the kinematism of the moving contacts the medium voltage terminals and the arcing chambers immersed in SF6 gas Reference Standards IEC 62271 100 CEI EN 62271 dossier 7642 5 2 Ba...

Page 10: ...o drilled supports in the lower part of the structure to allow the circuit breaker to be fixed The terminal box 17 is available for the electrical connections of the circuit breaker s auxiliary circuits in the front protection The earthing screw is located at the side of the circuit breaker Key 1 SF6 gas pressure signalling device on request only for circuit breakers with pressure switch 2 PR521 o...

Page 11: ...e in order to facilitate this operation The HD4 UniAir plug in circuit breaker can be set in the follow ing positions Plugged in Main circuits and auxiliary circuits connected Withdrawn Main circuits and auxiliary circuits disconnected Circuit breaker completely withdrawn from the compartment Key 1 Isolating contacts 2 Wheels 3 Release lever 4 Trolley on request 5 Connector The HD4 UniAir 2R plug ...

Page 12: ...inal duty value kPa 380 380 380 380 Application of PR521 protection device In A 40 80 250 1250 4 40 80 250 1250 4 40 80 250 1250 4 Application of REF 601 protection device 5 5 5 Standardized dimensions table TN 7237 1 TN 7237 1 TN 7237 1 TN 7238 TN 7234 2 TN 7234 2 TN 7234 2 Wiring diagram without protection device installed 1VCD400017 1VCD400017 1VCD400017 1VCD400017 with PR521 1VCD400017 1VCD400...

Page 13: ...521 protection device In A 40 80 250 1250 2 40 80 250 1250 2 Application of REF 601 protection device 3 3 Standardized dimensions table see note 4 see note 4 TN 7236 TN 7236 TN 7236 Wiring diagram without protection device installed 1VCD400018 1VCD400018 1VCD400018 with PR521 1VCD400018 1VCD400018 with REF 601 1VCD400116 1VCD400116 Operating temperature C 5 40 5 40 5 40 Tropicalization IEC 60068 2...

Page 14: ...thout relay with PR521 1VCD400017 4 1VCD400017 4 1VCD400017 4 1VCD400018 5 1VCD400018 5 1VCD400018 5 with REF 601 1VCD400114 4 1VCD400114 4 1VCD400114 4 1VCD400116 5 1VCD400116 5 1VCD400116 5 Operating temperature C 5 40 5 40 5 40 Tropicalization IEC 60068 2 30 60721 2 1 Electromagnetic compatibility IEC 62271 1 1 increase the indicated weight by 20 kg for circuit breakers with PR521 REF 601 devic...

Page 15: ...ensions table TN 7235 4 1VCD000102 4 1VCD000102 4 TN 7274 5 1VCD000103 5 1VCD000103 5 TN 7273 6 1VCD000104 6 1VCD000104 6 TN 7275 7 1VCD000104 6 1VCD000104 6 Wiring diagram without relay with PR521 1VCD400018 4 5 6 1VCD400018 4 5 6 1VCD400018 4 5 6 1VCD400017 7 1VCD400017 7 1VCD400017 7 with REF 601 1VCD400116 4 5 6 1VCD400116 4 5 6 1VCD400116 4 5 6 1VCD400114 7 1VCD400114 7 1VCD400114 7 Operating...

Page 16: ...ure nominal duty value kPa 380 380 380 Application of PR521 protection device In A application not available Application of REF 601 protection device 2 2 2 Standardized dimensions table 1VCD003536 1VCD003536 1VCD003536 Wiring diagram with without REF 601 1VCD400119 1VCD400119 1VCD400119 Operating temperature C 5 40 5 40 5 40 Tropicalization IEC 60068 2 30 60721 2 1 Electromagnetic compatibility IE...

Page 17: ...the coupling position of the handle provided with the hub 8 on the loading shaft fully insert it on the shaft itself and turn in a clockwise direction until the springs loaded signal yellow appears in the window 7 The force normally applied to the loading lever supplied is 130 N In any case the maximum force applied must not ex ceed 170 N 6 3 2 Closing spring loading lever If connected to the elec...

Page 18: ...there is a shunt closing release the closing operation can be obtained by remote control NOTE The closing pushbutton is not available for the re movable version of the circuit breakers HAD UniAir with out PR521 protection release 6 3 5 Opening operation Press the opening pushbutton 3 Opening is displayed by the letter O in the green part of the window 6 If there is a shunt opening release the clos...

Page 19: ...ded rest must be on the same plane to avoid any risk of distortion in the breaker structure A minimum degree of protection IP2X must be guaranteed from the front towards live parts The apparatus can be fixed in the following ways by means of special expansion anchoring bolts with M8 threaded hole if the apparatus is fixed to a cement floor by means of M8 bolts if the apparatus is fixed to metal st...

Page 20: ... washer between the head of the bolt and the connection The diameter of the flat washers must be able to distribute the torquing pressure over a wide area Tighten the bolt taking care to prevent the insulating parts from being stressed consult the table with the rightening torque values Make sure that the connections do not exert any force on the terminals Carefully comply with the manufacturer s ...

Page 21: ...21 7 9 Overall dimensions 7 9 1 Fixed HD4 R 12 24 kV 630 1250 A TN 7237 Figure 9 ...

Page 22: ...22 7 9 2 Fixed HD4 R 12 24 kV 630 1250 A TN 7234 Figure 10 ...

Page 23: ...23 Type A A B C 630 307 5 35 8 800 1250 302 5 40 10 7 9 3 Fixed HD4 R 36 kV 630 1250 A TN 7238 Figure 11 ...

Page 24: ...24 7 9 4 Plug in HD4 S 12 24 kV 630 1250 A TN 7236 Figure 12 ...

Page 25: ...25 7 9 5 HD4 Uniair 12 24 kV 630 1250 A TN 7235 Figure 13 ...

Page 26: ...26 7 9 6 HD4 Uniair F 12 24 kV 630 A TN 7275 Figure 14 ...

Page 27: ...27 7 9 7 HD4 Uniair 2R 12 24 kV 630 1250 A TN 7274 Figure 15 ...

Page 28: ...28 7 9 8 HD4 Uniair A 12 24 kV 630 1250 A TN 7273 Figure 16 ...

Page 29: ...29 7 9 9 HD4 UniMix F 12 24 kV 630 1250 A TN 7366 Figure 17 ...

Page 30: ...30 7 9 10 HD4 R SEC 12 24 kV 630 800 A 1VCD003536 Figure 18 ...

Page 31: ...ke sure that the connections to the control circuit are correct proceed with the relative power supply Normal operations and signals 3 Manual operating mechanism Perform a few closing and opening operations see chap 6 NOTE Power the undervoltage release and the locking magnet on the operating mechanism at the relative rated voltage if provided The operations and relative signals occur correctly 4 ...

Page 32: ... See sect 8 1 point 1 5 Checking interlock operation Every 5 years or after every 5 000 operations The interlocks provided must function correctly Warning Contact the ABB Assistance Service and have the circuit breaker completely overhauled after 10 000 operations or after 10 years 9 3 Troubleshooting The shunt opening and or shunt closing release remains energized Faults The shunt opening and or ...

Page 33: ...10 4 2 If maintenance is carried out by the customer s personnel responsibility for the interventions remains with the customer Replacement of parts not included in the List of spare parts accessories sect 12 1 must only be carried out by ABB personnel In particular complete pole with bushings connections operating mechanism closing spring set opening spring ...

Page 34: ...ogy The environmental impact of any specific application should be evaluated and or compared using the Life Cycle Assess ment LCA approach as established by ISO 14040 standards The Electric Industry uses SF6 in a closed cycle e g in the circuit breakers of gas insulated substations GIS in medium voltage and high voltage gas insulated circuit breakers GCB in igh voltage gas insulated lines GIL and ...

Page 35: ... spare parts Accessories Opening release Undervoltage release Contact for signalling undervoltage release energised de energised Time delay device for undervoltage release Mechanical override for undervoltage release Closing release Spring loading geared motor with electrical signalling of springs loaded Gearmotor thermomagnetic protection circuit breaker Contact for signalling gearmotor protectio...

Page 36: ...es its skills and assistance to facilitate the recycling and disposal process for products at the end of their life It is always necessary to comply with the local regulations when disposing of products Disposal methods The products can be disposed of by means of heat treatments in incineration systems or by storage in dedicated areas Material Recommended disposal method Metals Fe Cu Al Ag Zn W ot...

Page 37: ......

Page 38: ...00900 Rev H en Instruction manual 2010 03 HD4 R mt a For further details please contact ABB S p A Power Products Division Unità Operativa Sace MV Via Friuli 4 I 24044 Dalmine Tel 39 035 6952 111 Fax 39 035 6952 874 E mail info mv it abb com www abb it ...

Reviews: