6.4.9 Auxiliary DC power outputs
The MV UPS provides 24 Vdc auxiliary power supply for the Energy Storage, Generators, and external Demand Re-
sponse Controllers.
Table 6.03 shows the terminals' configuration. The current on each output must not exceed 10 A.
Terminal
Number
Description
X6
1
Energy Storage Int24 Vdc
X6
2
Energy Storage Interface 0 Vdc
X7
1
Switchgear Int24 Vdc
X7
2
Switchgear Interface 0 Vdc
X8
1
Demand Response Controller Int24 Vdc
X8
2
Demand Response Controller Interface 0 Vdc
X23
1
Generator Int24 Vdc
X23
2
Generator Interface 0 Vdc
—
Table 6.03: Auxiliary DC