71
7.3.1 List of user accounts
The HiPerGuard includes an ABB Service account which is accessible via Secure Shell (SSH). No other accounts are
enabled for SSH access. Operator parameter setting to temporarily allow ABB access for Service actions.
SSH is disabled by default, however it can be enabled from the GDM through an Operator parameter setting to
temporarily allow ABB access for Service actions.
Username
Interface
Password Access
Enabled by default
pcs120admin
SSH
No
No
7.3.2 Ports and services
• Modbus TCP (read-only registers) on port 502. This port is disabled by default. Enable this MODBUS TCP
from the GDM services menu.
• Remote web interface for status/logs on port 80. This port is enabled by default.
• SSH interface for ABB Service on port 22. This port is disabled by default.
—
Table 7.09: List of
User accounts.
Summary of Contents for HiPerGuard MV UPS
Page 58: ...58 HIPERGUARD MV UPS USER MANUAL Figure 7 04 Pages map ...
Page 84: ......