39
—
Technical specifications
General product data
Product class
7.2 kV IEC
12kV IEC 15 kV ANSI 24kV IEC
General
Rated Voltage
6-6.6kV
10-11 kV
12.47-13.8kV 20-22kV
Rated apparent power
2250kVA
Single unit
Rated active power
2250kW
Load power
factor 1.0
Hard parallel configuration
Up to 10 units
Performance
Efficiency
98% for 50% to 100% loading
96% for 25% to 50% loading
Under nomi-
nal conditions
Dynamic output perfor-
mance
In line with IEC62040-3 VI SS 111
Architecture
ZISC enabled line interactive
—
Table 5.01: HiPerGuard
MV UPS General Data
—
5.1 Utility input
—
Table 5.02: HiPer-
Guard MV UPS Input
specifications
Input
Voltage tolerance
±10 %
From nominal voltage
Rated frequency
50 Hz/60 Hz
Frequency tolerance
± 2 %
From rated frequency
Displacement power factor at
supply
> 0.96
Under nominal conditions
Battery charging current
10-20%
Grid supplied on top of the load current
Power Distribution system
IT, 3-Wire Input
Please contact ABB for other distribution
systems
Current distortion THDi
< 3%
Full linear load, under nominal conditions,
operating on power conditioning mode.