5.2 Load output
—
Table 5.03: HiPer-
Guard MV UPS output
specifications
Output
Steady-state voltage variation
±1 %
Rated frequency
50 Hz or 60 Hz
Frequency accuracy
± 0.1%
Applicable to independent mode only
Load power factor range
0.9 leading to 0.8 lagging
Nominal power factor 1.0
Maximum fault clearing current
Independent mode
400%, 2 s
Power conditioning mode
500%, 2 s
Overload power ratings
Independent mode
125%, 30 s
Battery sizing dependent
Power conditioning mode
110%, 60 min
125%, 5 min
150%, 1 min
From nominal conditions
Power Distribution system
IT, 3-Wire Output
Please contact ABB for other distribution
systems
Voltage distortion THDv
< 2.5%
Full linear load, under nominal conditions,
operating on power conditioning mode
—
5.3 Energy Storage
—
Table 5.04: Energy
Storage specifications
Energy Storage
Type
Li-Ion batteries (not included)
Supplier
ABB qualified
Autonomy range
15 sec to 15 min
Voltage Range
520 Vdc to 750 Vdc
Inverter fast charging power
up to 225 kW
Auxiliary charger
Yes