6.4 Power and I/O interfaces to APS enclosure
6.4.1 External auxiliary 3-phase power supply input
An external power supply is required for system start-up. This is not needed once the system is running. The re-
quirements are summarized in Table 6.01.
—
Table 6.01: External A.C.
supply requirements
External A.C. supply
Supply
3-phase 50/60 Hz TN
Required supply current
10 A
Maximum prospective short-circuit current
25 kA
Input voltage
380-440 Vac
Voltage tolerance
+10%/-5%
6.4.2 Digital outputs
Five changeover relays are provided in the MV UPS, for status and alarm signaling. Each relay has a voltage-free
changeover contact, which is wired to terminals X10-1 to X10-15 inside the APS enclosure. Table 6.02 shows the
function of each relay and the wiring connections to these relay contacts.
The connection terminals are located in the APS enclosure on fuse holders F6-1, F6-3, and F6-5.
Digital Outputs
Rated voltage
Steady state current
Switching capacity
30 Vdc
5A
240 Vac
Terminal
Signal
Default setting
Description
X10-1
Warning
MV UPS machine warning sta-
tus
X10-2
X10-3
X10-4
Fault
MV UPS machine fault status
X10-5
X10-6
X10-7
Run
MV UPS machine is running
X10-8
X10-9
X10-10
Independent mode
MV UPS is operating on inde-
pendent mode
X10-11
X10-12
X10-13
Insulation
MV UPS insulation monitor
status
X10-14
X10-15
—
Table 6.02: Status
feedback relay func-
tions and wiring.