6.5 Communication between MV UPS and MV
Switchgear
There is a high-speed optical communication link between the HiPerGuard MV UPS’s main controller and the
switchgear. The purpose of the link is to read and write information from/to the I/O modules installed in the MV
switchgear. The breakers’ status, current, voltage, and commands (open/close) to the circuit breakers (Sin, Sout,
Sabp) are transmitted through fiber optic.
Using HCS (hard-clad silica) cables, the maximum cable length from the APS cabinet coupler to the controller lo-
cated in the switchgear is 120 m. A pair of 120 m long HCS fiber optic cables, ready for installation is issued by
ABB. The connectors are located on the bottom of the APS cabinet, as shown in Figure 6.09
—
Figure 6.08: Control
interconnections MV
UPS to MV switchgear .