Operation Manual / 4 Product description / A130-M.. - A145-M..
7
Eliminating malfunctions
Page 66 / 121
© Copyright 2017 ABB. All rights reserved.
HZTL4031_EN
Revision E
January 2017
7.2
Malfunctions during operation
Lubricating oil pressure too low
WARNING
Danger of fire and explosion due to lubricating oil leaks
Leaking oil may ignite on hot surfaces. This can result in serious injuries to
personnel or fatal accidents.
Cordon off danger area.
Raise the alarm and, depending on the situation, stop the engine.
Seal the oil leak.
Soak up oil and dispose of in an environmentally compatible manner.
Wear safety gloves to protect against thermal hazards.
Possible causes
Remedy
Engine
Oil filter heavily contaminated
Clean
Oil pump in lubricating system defective
Check/replace
Manometer displays incorrectly
Replace manometer
Turbocharger Axial clearance of the rotor excessive
Contact ABB Turbocharging Service
Station
Table 19: Malfunctions during operation – Lubricating oil pressure too low
Speed reduces
Possible causes
Remedy
Engine
Defect on the connected cylinders in pulse
charging
Contact enginebuilder
Turbocharger Turbine and/or nozzle ring severely con-
taminated
Clean (see chapter Periodic maintenance
Rotor components or bearing damaged
Contact ABB Turbocharging Service
Station
Pipes
Defects, such as leaks, in the exhaust gas
pipes or charge air ducts
Repair
Table 20: Malfunctions during operation – Speed reduces
Speed increases
Possible causes
Remedy
Turbocharger Light to medium contamination of the tur-
bine and/or nozzle ring (with 4-stroke ap-
plication)
Clean (see chapter Periodic maintenance
45]) or contact an ABB Turbo-
charging Service Station
Table 21: Malfunctions during operation – Speed increases