General
© 2006 ABB STOTZ-KONTAKT GmbH
5
ABB i-bus
®
EIB / KNX
1.1
Product and functional
overview
The Data Logging Unit BDB/S 1.1 is a modular installation device for fast
installation in the distribution board with a module width of 2 space units.
The Data Logging Unit enables you to count the switching operations of
switch actuator channels in an ABB i-bus
®
system. Furthermore, the
operating hours of the connected loads can be recorded with a resolution of
up to one second. 35 independent channels are available each with seven
communication objects provided. The switching operations as well as the
operating hours can be recorded on a channel basis, where the counting
method from zero upwards or from a set value downwards can be selected.
The operating data of every channel is derived from the state of the
communication object
Channel X switch position – received
.
Via a communication object or parameter it is possible to define the
corresponding start or limit value for each individual switch operation counter
value. With a total value mode of counting, i.e. counting from zero up to a set
limit value, an alarm message is generated if the limit value is exceeded.
With a remaining value mode of counting, i.e. counting from an adjustable
start value down to zero, an alarm message is generated if zero is reached.
Via a communication object or parameter it is possible to define the
corresponding start or limit value for each individual operating hours counter
value. With a total run time mode of counting, i.e. counting from zero up to
set limit value, an alarm message is generated if the limit value is exceeded.
With a remaining run time mode of counting, i.e. counting from adjustable
start value down to zero, an alarm message is generated if the zero is
reached.
The counter values and start or limit values can be changed via the bus.
The values can only be modified after enabling via a communication object.
Via the communications object “Delete all operating data - System” all
operating data can be deleted in the Data Logging Unit.
Every state change adjustable via parameters increments the current
counter value of the operations counter by one.
The level to count the operating hours can be defined via a parameter.
The Data Logging Unit can even be set to count permanently via the level
setting. Counting is undertaken every second.
During a new start the switching states of the monitored switch actuator
channels are read after a settable time. A pause can be programmed
between the two corresponding telegrams. If a switch actuator does not
respond, the telegram will be repeated twice.
On bus voltage failure all counter values and start or limit values are saved
in BDB/S 1.1 and restored when the bus voltage recovers. If the limit values
are exceeded the Data Logging Unit sends the respective alarm messages
on the ABB i-bus
®
.