For installation in the distribution board. The device is used for recording of
switching operations and operating hours on 35 channels. The BDB/S 1.1 is
operational after of the bus voltage. The module is programmed directly via
the application program ETS. The connection to the ABB i-bus
®
is
established via the bus connection terminal at the front of the device.
Fig. 1:
BDB/S 1.1
2.1 Technical
data
Power supply
- Bus voltage
21 … 32V DC
- Current consumption, bus
< 12 mA
- Leakage loss, bus
Max. 250 mW
Connections
- EIB / KNX
via bus connection terminals
Operating and display elements
- Programming LED
for assignment of the physical address
- Programming button
for assignment of the physical address
Enclosure
- IP 20
to DIN EN 60 529
Safety class
- II
to DIN EN 61 140
Isolation category
Overvoltage category
III to DIN EN 60 664-1
Pollution degree
2 to DIN EN 60 664-1
EIB / KNX safety extra low voltage
SELV 24 V DC
Temperature range
- Operation
- Storage
- Transport
-5° C…+ 45° C
-25°C…+ 55°C
-25°C…+ 70°C
Ambient conditions
- Maximum air humidity
93%, no condensation allowed
Design
- Modular installation device (MDRC)
Modular installation device, Pro
M
- Dimensions
90 x 36 x 64.5 mm (H x W x D)
- Mounting width in space units
2 (2 modules at 18 mm)
- Mounting depth
64.5 mm
Installation
- On 35 mm mounting rail
to DIN EN 60 715
Mounting position
- as required
Weight
– 0.1 kg
Housing/colour
- Plastic housing, grey
Approvals
- EIB / KNX to EN 50 090-1, -2
Certification
CE mark
- in accordance with the EMC guideline and
-
low voltage guideline
Table 1:
Technical data
2CDC
07
1 2
47 F
0
006