15
ABB i-bus
®
KNX
Technical data and connection
The parameterisation of the gateway and the DALI equipment is carried out
with the application software
“Dim Slave Lightscenes Dynamic 8f/1.1”
and
the ETS software (from version ETS2V1.3 onwards). When using ETS3, a file
of type “.VD3” must be imported. The following tasks must be carried out:
– Assignment of the physical KNX device addresses of the
DALI Gateway
– Parameterisation of the lighting behaviour of the DALI devices
(e.g. dimming speed, starting value, transitional period etc.)
– Definition and setting of lightscenes
– Parameterisation of the KNX control
(e.g. setting flags and defining telegram transmission times)
– Parameterisation of the status functions and behaviour in the event
of a fault
– Assignment of the communication objects to KNX groups
The installation and commissioning may only be carried out
by specialist electricians. When planning and installing electrical
installations, the appropriate norms, guidelines, regulations and
specifications must be reserved.
To be able to commission the DALI-Gateway DG/S 8.1, it must be
connected to an AC or DC 230 V power supply. You require a PC or laptop
with ETS (from ETS2 V1.3 onwards) and an interface to the ABB i-bus
®
e.g. via RS232 or USB interface.
The DALI-Gateway DG/S 8.1 is supplied with the physical address
15.15.255. The connecting terminals are open and the bus connection
terminal is premounted.
The assignment of the physical KNX address of the DALI-Gateway
DG/S 8.1 is carried out via the ETS and the programming button on the
device.
The DALI-Gateway DG/S 8.1 has a programming button for assigning the
KNX physical address which is located on the shoulder of the device. Once
the button has been pressed, the red programming LED lights up. It is extin-
guished as soon as the ETS program has assigned the physical address or
the programming button has been pressed again.
Green-LED lights up,
When power is available and the device is ready for operation
Yellow-LED lights
Up:
in normal operation
,
Blinks:
if DALI fault in Test
Operation
, if Gateway in Test Operation
Red LED lights up,
If the device is in the programming mode (after the programming key has
been pressed).
2.6.1
Commissioning
requirements
2.6.2 Supplied
state
2.6.3
Assignment of the physical
KNX address
2.6.4 Display
elements