25
ABB i-bus
®
KNX
7
Telegr. Fault Ballast
Channel A
1 bit (EIS 1)
DPT 1.005
C, R, T
Channel X Telegr. Fault Ballast [EIS 1; 1-bit switching]:
A fault signal which originates
from one or more ballasts of the channel can be sent or read out via this object (e.g. for main-
tenance purposes), depending on the parameter setting (
Status
parameter window).
The communication object is only visible if the parameter option “Send telegram ‘Fault
Ballast’” has been activated in the
Status
parameter window.
Telegram value
“1”: Fault of one or more ballasts of the channel
“0”: No fault
To guarantee correct operation, the gateway must know how many
ballasts need to be monitored. This is carried out by activating the object
“Detect Ballasts”. With this function, the DALI Gateway establishes
automatically how many ballasts are connected and uses this number
as a reference value. If the installation should be extended or reduced,
the option “Detect Ballasts” must be activated again. This process is
necessary if the number of ballasts per channel has changed and not
when replacing a ballast in the same channel.
8
Telegr. Fault Lamp
Channel A
1 bit (EIS 1)
DPT 1.005
C, R, T
Channel X Telegr. Fault Lamp [EIS 1; 1-bit switching]:
A lamp fault (e.g. failure) which has
been caused by one or more ballasts of the channel can be sent or read out via this object
(e.g. for maintenance purposes), depending on the parameter setting (
Status
parameter
window). The communication object is only visible if the parameter option “Send telegram
‘Fault Lamp’” has been activated in the
Status
parameter window.
Telegram value
“1”: Fault with one or more lamps of the channel
“0”: No fault
9
Telegr. Fault DALI
Channel A
1 bit (EIS 1)
DPT 1.005
C, R, T
Channel X Telegr. Fault DALI [EIS 1; 1-bit switching]:
A fault in the DALI communication
of the channel (i.e. short circuit) can be sent or read out (e.g. for maintenance purposes) via
this object, depending on the parameter setting (
Status
parameter window). The communica-
tion object is only visible if the parameter option “Send telegram ‘Fault DALI’” is activated
in the
Status
parameter window.
Telegram value
“1”: Fault in the DALI communication of the channel
“0”: No fault
Continuation Table 4: Communication objects “Channel X”
The corresponding communication objects 10 to 79 apply for the DALI
outputs (channels) B to H.
Project design and programming