22
ABB i-bus
®
EIB / KNX
The same conversion factor leads the actuator in the opposite direction for
the “Status” communication object. The status object sends the new value
with the following results:
쐌
When the input value object receives a new value which differentiates
from the current output value.
쐌
If the output has received a new value, because a control with a higher
priority has been activated or deactivated by a “forced control” object.
쐌
If the output receives a new incoming telegram but does not execute it
because a forced control is active.
Example
The output is set to 9 volts due to a forced control. The “Input value”
object receives the value 5 volts. The value is not set due to the forced
control. The status object reports back with the 9 volts value. The new
input value of 5 volts is stored internally and set as soon as the forced
control has ended. The status object reports the value of 5 volts.
쐌
If the time for monitoring of the “Input value” and/or “Forced control”
communication objects has timed out.
Planning and application