ABB i-bus
®
KNX
Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 213
7.5.1.9.1.2.5
—
Dependent Parameter
Extended settings
Options:
No
Yes
Extended settings can be enabled using this parameter. This parameter is displayed on the selec-
tion of the
Yes
option.
7.5.1.9.1.2.5.1
—
Dependent Parameter
Control value direction
This parameter is only visible if the
Via group object
option has been selected for the
Actuate
additional-stage cooling via
parameter in the
Application parameters
parameter window.
Options:
Normal
Inverted
This parameter is used to specify the control value direction if it is only output via a group object.
The setting is used to actuate NC (normally closed) or NO (normally opened) valves.
If one of the physical device outputs is used to output the control value, this parameter is not dis-
played because this setting is then made in the related output stage.
•
Normal
: The control value is output normally.
Control value On/100 % => telegram Off/0 %
Control value Off/0 % => telegram On/100 %
•
Inverted
: The control value is output inverted.
Control value On/100 % => telegram Off/0 %
Control value Off/0 % => telegram On/100 %
7.5.1.9.1.2.5.2
—
Dependent Parameter
Control value difference for sending control value
This parameter is only visible on the selection of the
PI continuous (0…100 %)
or
PI continuous
(0...100 %) for Fan Coil
option.
Options:
2 %
5 %
10 %
Only send cyclically
The control values for the PI continuous controller 0…100 % are not sent after each calculation,
but when there is a difference in the calculation compared to the last value sent and sending is ap-
propriate. This value difference can be entered here.