ABB i-bus
®
KNX
Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 224
7.6.4.1
Selection of Absolute
7.6.4.1.1
—
Dependent Parameter
Standby heating setpoint
This parameter is only visible if the device has been parameterized for heating and the
Deactivated
option has not been selected for the
Basic-stage heating
parameter in the
Application parameters
parameter window, and the
Setpoint specification and adjustment
parameter has been parameter-
ized with the
Absolute
option.
Options:
10…19…40
This parameter is used to set the temperature that is to apply in the Standby operating mode in the
type of operation heating.
Note
The temperature stated here must be lower than the temperature selected in the
Comfort heating
setpoint
or
Setpoint for Comfort heating and cooling
parameter. A temperature that is at least
2 °C lower is recommended.
The controller does not change the type of operation to reach this temperature, instead it ensures
this temperature is not dropped below on a reduction in the actual temperature.
7.6.4.1.2
—
Dependent Parameter
Economy heating setpoint
This parameter is only visible if the device has been parameterized for heating and the
Deactivated
option has not been selected for the
Basic-stage heating
parameter in the
Application parameters
parameter window, and the
Setpoint specification and adjustment
parameter has been parameter-
ized with the
Absolute
option.
Options:
10…17…40
This parameter is used to set the temperature that is to apply in the Economy operating mode in
the type of operation heating.
Note
The temperature stated here must be lower than the temperature selected in the
Standby heating
setpoint
parameter. A temperature that is at least 2 °C is recommended.
The controller does not change the type of operation to reach this temperature, instead it ensures
this temperature is not exceeded on an increase in the actual temperature.