ABB i-bus
®
KNX
Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 262
7.8.1.2.1.2.2.1
—
Dependent Parameter
Control value
Options:
0…100
This parameter is used to specify the control value that is to be set after bus voltage recovery, ETS
download and ETS reset.
Note
The value set after bus voltage recovery, ETS download and ETS reset applies until a new con-
trol value is received via the
Control value VAV damper control A
group object.
7.8.1.2.1.2.3
—
Dependent Parameter
Send status values
Options:
On request
On change
Cyclically
After a change or on request
After a change or request and cyclically
This parameter defines when the
Status Control value
for the VAV damper output is to be sent.
•
On request
: The status value is sent on the receipt of a command via the
Request status values
group object.
•
On change
: The value is sent on a change to the control value if the change in the control value
is at least 1 %.
•
Cyclically
: If this option is selected, the status value is sent automatically after an adjustable
time has elapsed. The
Every
dependent parameter is displayed.
•
After a change or request
: The value is sent on request and on a change.
•
After a change or request and cyclically
: The value is sent on request and on a change and
cyclically. The
Every
dependent parameter is displayed.
7.8.1.2.1.2.3.1
—
Dependent Parameter
Every
Options:
00:00:30…00:05:00…18:12:15
This parameter is used to set the time after which the status values are to be sent cyclically. The
group objects are sent after each cycle.