ABB i-bus
®
KNX
Group objects
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 319
No.
Function
Name
Data Point Type
(DPT)
Length
Flags
C
R
W T
U
41
Enable/disable manual override valve
Channel – Valve B
1.003
1 bit
X
X
42
Override valve control value
Channel – Valve B
5.001
1 byte
X
X
43
Control value VAV damper control
Channel – Valve B
5.001
1 byte
X
X
44
Status Relay
Channel – Relay
1.009
1 bit
X
X
X
45
Switch relay
Channel – Relay
1.001
1 bit
X
X
46
Forced operation 2 bit
Channel – General
2.001
2 bits
X
X
47
Forced operation 1 bit
Channel – General
1.002
1 bit
X
X
48
Error: heating/cooling receipt
Channel – General
1.002
1 bit
X
X
X
49
Error: window status receipt
Channel – General
1.002
1 bit
X
X
X
50
Error: dew point status receipt
Channel – General
1.002
1 bit
X
X
X
51
Error: fill level status receipt
Channel – General
1.002
1 bit
X
X
X
52
Error: operating mode receipt
Channel – General
1.002
1 bit
X
X
X
53
Temperature
Channel – Input a
9.001
2 bytes
X
X
X
54
Input error
Channel – Input a
1.002
1 bit
X
X
X
55
Switch
Channel – Input a
1.001
1 bit
X
X
X
55
Window contact
Channel – Input a
1.019
1 bit
X
X
X
55
Dew point alarm
Channel – Input a
1.005
1 bit
X
X
X
55
Fill level alarm
Channel – Input a
1.005
1 bit
X
X
X
56
Disable input
Channel – Input b
1.003
1 bit
X
X
57
Temperature
Channel – Input b
9.001
2 bytes
X
X
X
58
Input error
Channel – Input b
1.002
1 bit
X
X
X
59
Switch
Channel – Input b
1.001
1 bit
X
X
X
59
Window contact
Channel – Input b
1.019
1 bit
X
X
X
59
Dew point alarm
Channel – Input b
1.005
1 bit
X
X
X
59
Fill level alarm
Channel – Input b
1.005
1 bit
X
X
X
60
Disable input
Channel – Input b
1.003
1 bit
X
X
61
Temperature
Channel – Input c
9.001
2 bytes
X
X
X
62
Input error
Channel – Input c
1.002
1 bit
X
X
X
63
Switch
Channel – Input c
1.001
1 bit
X
X
X
63
Window contact
Channel – Input c
1.019
1 bit
X
X
X
63
Dew point alarm
Channel – Input c
1.005
1 bit
X
X
X
63
Fill level alarm
Channel – Input c
1.005
1 bit
X
X
X
64
Disable input
Channel – Input c
1.003
1 bit
X
X
65
Temperature
Channel – Input d
9.001
2 bytes
X
X
X
66
Input error
Channel – Input d
1.002
1 bit
X
X
X
67
Switch
Channel – Input d
1.001
1 bit
X
X
X
67
Window contact
Channel – Input d
1.019
1 bit
X
X
X
67
Dew point alarm
Channel – Input d
1.005
1 bit
X
X
X
67
Fill level alarm
Channel – Input d
1.005
1 bit
X
X
X
68
Disable input
Channel – Input d
1.003
1 bit
X
X
69
Status Heating/Cooling
Channel – Controller 1.100
1 bit
X
X
X
70
Status Control value Basic-stage heating
Channel – Controller 5.001
1 byte
X
X
X