ABB i-bus
®
KNX
Group objects
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 327
No.
Function
Group object name Data Type
Flag
23
Limitation 1
Channel – Fan
1 bit
DPT 1.003
C, W
This group object is enabled if the parameter
Fan speed limitation
is set to
Activated
in the
Fan output
pa-
rameter window.
Limitation 1 is active when a telegram with the value 1 is received on the group object
Limitation 1
. Limitation
1 is canceled when a telegram with the value 0 is received on the group object
Limitation 1
.
When Limitation 1 is activated, the fan can assume the only the fan speed or speed range as set in the pa-
rameter
Limitation 1
.
Telegram value:
•
0 = Limitation x inactive
•
1 = Limitation x active
24
Limitation 2
Channel – Fan
1 bit
DPT 1.003
C, W
See group object 23
25
Limitation 3
Channel – Fan
1 bit
DPT 1.003
C, W
See group object 23